1.Product Description
The flame detectors uses 2 infrared sensors with different wavelengths with narrow-band filtering. One sensor is used to reflect the center wavelength of the flame information. The other sensor is used to monitor other infrared radiation in the environment. Combining with the flicker characteristics of the flame, analyzing through high-speed microprocessors and calculating by mathematical algorithms, the radiation spectrum with flame characteristics is confirmed as a fire alarm.The detector suppress the interference of sunlight, lightning, electric welding, thermal radiation, electromagnetic interference, mechanical vibration and other interference, thus achieving the rapid response and accurate identification of the flame signal.
2.Technical Data
| Response spectral range | 4.4μm, 3.8μm |
| Response time | 15s |
| Viewing angle range | ≤110° |
| Detection distance | Class I |
| Ambient temperature | -10 ~ 55 ℃ |
| Environmental humidity | ≤95% RH |
| Pressure range | 86 ~ 106Kpa |
| Working voltage | DC24V |
| Working current | current≤25mA, alarm current≤35mA |
| Explosion-proof grade | EXdⅡCT6 |
| Protection grade | IP66 |
3.Mechanical structure
1)Installation method: wall or ceiling
2)Cable outlet thread: 20mmX1.5mm free conversion G1 / 2 optional
3)Dimensions: (190X160X110) mm
4)Shell material: die-cast aluminum
5)Weight: 1Kg
6)Advantages: dustproof, explosion-proof, corrosion-proof
4. Product Selections


It-tags Popolari: industrial ir2 double infrared flame detector for oil gas station